R-22 Models General Data
|

|
R-404A Models
|

|
Technician Information
|
KJ(L) 500 / 5 H.P. (5 x 1) / R-22
|
Saturated Suction Temperature / Evaporating Temperature
|
|
0ºF
-17.7ºC
|
5ºF
-15ºC
|
10ºF
-12.2ºC
|
15ºF
-9.4ºC
|
20ºF
-6.6ºC
|
25ºF
-3.8ºC
|
30ºF
-1.1ºC
|
35ºF
1.6ºC
|
40ºF
4.4ºC
|
A
m
b
i
e
n
t
T
e
m
p
|
70ºF
21.1ºC
|
26,850
BTUs
|
28,300
BTUs
|
32,600
BTUs
|
37,300
BTUs
|
42,300
BTUs
|
47,600
BTUs
|
53,500
BTUs
|
59,500
BTUs
|
65,500
BTUs
|
80ºF
26.7ºC
|
22,700
BTUs
|
26,500
BTUs
|
30,600
BTUs
|
35,100
BTUs
|
40,000
BTUs
|
45,300
BTUs
|
51,000
BTUs
|
57,000
BTUs
|
63,000
BTUs
|
90ºF
32.2ºC
|
21,300
BTUs
|
24,800
BTUs
|
28,700
BTUs
|
33,000
BTUs
|
37,600
BTUs
|
42,700
BTUs
|
48,000
BTUs
|
54,000
BTUs
|
60,000
BTUs
|
(15ºF Super heat, 10ºF Subcooling and with R-22 Refrigerant.
For environments with ambient temperatures above 90ºF, please contact us directly.)
|
Electricals
|
Evap. Motor
|
Amps
|
Cond. Motor
|
Amps
|
Compressor
|
Amps
|
Total Amps *
|
|
230/1/60
|
3/4 HP x 2
|
7.2
|
3/4 HP x 1
|
3.6
|
5 HP x 1
|
20 x 1
|
30.8
|
|
208/3/60
|
3/4 HP x 2
|
7.2
|
3/4 HP x 1
|
3.6
|
5 HP x 1
|
13.5 x 1
|
24.3
|
|
575/60
|
3/4 HP x 2
|
2.4
|
3/4 HP x 1
|
1.2
|
5 HP x 1
|
5 x 1
|
8.6
|
(* Comp. Amps are based on 40ºF SST, 110ºF COND., 20ºF Super heat, 15ºF Subcooling and with R-22 Refrigerant.)
KJ(L)500 Central Airflow Design


|
KJ(L)500 Up Airflow Design


|
 |
KJ(L)500 Down Airflow Design


|
|

|

|