R-22 Models General Data
|

|
R-404A Models
|

|
Technician Information
|
KJ(L) 3000 / 27 H.P. (13.5 x 2) / R-22
|
Saturated Suction Temperature / Evaporating Temperature
|
|
0ºF
-17.7ºC
|
5ºF
-15ºC
|
10ºF
-12.2ºC
|
15ºF
-9.4ºC
|
20ºF
-6.6ºC
|
25ºF
-3.8ºC
|
30ºF
-1.1ºC
|
35ºF
1.6ºC
|
40ºF
4.4ºC
|
A
m
b
i
e
n
t
T
e
m
p
|
70ºF
21.1ºC
|
139,400
BTUs
|
160,800
BTUs
|
184,400
BTUs
|
210,500
BTUs
|
239,100
BTUs
|
270,500
BTUs
|
304,800
BTUs
|
342,100
BTUs
|
382,600
BTUs
|
80ºF
26.7ºC
|
126,800
BTUs
|
147,100
BTUs
|
169,500
BTUs
|
194,200
BTUs
|
221,400
BTUs
|
251,200
BTUs
|
283,700
BTUs
|
319,200
BTUs
|
357,800
BTUs
|
90ºF
32.2ºC
|
114,700
BTUs
|
133,700
BTUs
|
154,800
BTUs
|
178,000
BTUs
|
203,600
BTUs
|
231,600
BTUs
|
262,300
BTUs
|
285,500
BTUs
|
332,200
BTUs
|
(15ºF Super heat, 10ºF Subcooling and with R-22 Refrigerant.
For environments with ambient temperatures above 90ºF, please contact us directly.)
|
Electricals
|
Evap. Motor
|
Amps
|
Cond. Motor
|
Amps
|
Compressor
|
Amps
|
Total Amps *
|
|
208/3/60
|
1.5 HP x 5
|
43
|
3/4 HP x 5
|
18
|
13 HP x 2
|
32.7 x 2
|
126.4
|
|
575/3/60
|
1.5 HP x 5
|
10
|
3/4 HP x 5
|
6
|
13 HP x 2
|
13.1 x 2
|
42.2
|
(* Comp. Amps are based on 40ºF SST, 110ºF COND., 20ºF Super heat, 15ºF Subcooling and with R-22 Refrigerant.)
KJ(L)3000 Central Airflow Design


|
KJ(L)3000 Up Airflow Design


|
 |
KJ(L)3000 Down Airflow Design


|
|

|

|