R-22 Models General Data
|

|
R-404A Models
|

|
Technician Information
|
KJ(L) 2000 / 21 H.P. (10.5 x 2) / R-22
|
Saturated Suction Temperature / Evaporating Temperature
|
|
0ºF
-17.7ºC
|
5ºF
-15ºC
|
10ºF
-12.2ºC
|
15ºF
-9.4ºC
|
20ºF
-6.6ºC
|
25ºF
-3.8ºC
|
30ºF
-1.1ºC
|
35ºF
1.6ºC
|
40ºF
4.4ºC
|
A
m
b
i
e
n
t
T
e
m
p
|
70ºF
21.1ºC
|
110,400
BTUs
|
127,700
BTUs
|
146,800
BTUs
|
167,700
BTUs
|
190,700
BTUs
|
215,800
BTUs
|
243,100
BTUs
|
272,800
BTUs
|
305,000
BTUs
|
80ºF
26.7ºC
|
100,200
BTUs
|
116,600
BTUs
|
134,700
BTUs
|
154,600
BTUs
|
176,400
BTUs
|
200,200
BTUs
|
226,200
BTUs
|
254,400
BTUs
|
285,000
BTUs
|
90ºF
32.2ºC
|
90,500
BTUs
|
105,900
BTUs
|
122,900
BTUs
|
141,600
BTUs
|
162,100
BTUs
|
184,500
BTUs
|
208,900
BTUs
|
235,500
BTUs
|
264,400
BTUs
|
(15ºF Super heat, 10ºF Subcooling and with R-22 Refrigerant.
For environments with ambient temperatures above 90ºF, please contact us directly.)
|
Electricals
|
Evap. Motor
|
Amps
|
Cond. Motor
|
Amps
|
Compressor
|
Amps
|
Total Amps *
|
|
208/3/60
|
3/4 HP x 4
|
14.4
|
3/4 HP x 4
|
14.4
|
10.5 HP x 2
|
28.5 x 2
|
85.8
|
|
575/3/60
|
3/4 HP x 4
|
4.8
|
3/4 HP x 4
|
4.8
|
10.5 HP x 2
|
11.4 x 2
|
32.4
|
(* Comp. Amps are based on 40ºF SST, 110ºF COND., 20ºF Super heat, 15ºF Subcooling and with R-22 Refrigerant.)
KJ(L)2000 Central Airflow Design


|
KJ(L)2000 Up Airflow Design


|
 |
KJ(L)2000 Down Airflow Design


|
|

|

|